High Reliability

  • Wide input voltage range +/- 20% (up to -40% at reduced load)
  • Hot-swappable function ensures uninterrupted operations during maintenance
  • Dual system control card prevents single failure point
  • Intelligent fan control and redundant design for energy saving: 25% load can be driven when 2 fans
    fail and 50% load when 1 fan fails
  • Parallel expansion up to four systems without requiring additional hardware

High Performance

  • High efficiency in online mode (>97%) reduces heat dissipation and limits power consumption costs
  • THDi≤3% and input power factor 0.99 reduce the pollution to grid and reduce upstream investment costs
  • Full rated power (kVA=kW) to maximize power availability
  • Efficiency>99% in ECO mode gives significant cost reduction
  • Advanced power module sleep mode, prolong the service life of power module
  • Allow 100% three phase unbalance load
  • Frequency converter function(60Hz to 50Hz or 50Hz to 60Hz)
  • Loop test function without load enables on-site commission
  • Small footprint, 300kW only covers 0.5m2
MODEL X-PND 60 X-PND 90 X-PND 120
Power module Model XPD - 30
Input
Voltage Range (Vac) 3Φ4W+PE, 380/400/415, L-L: 138~485
Input Wiring 3Ph+N+PE
Input Frequency (Hz) 40-70
Bypass Voltage Range (Vac) -15% (-20%/-30% optional) ~+15%(+10% /+20% optional)
Power Factor ≥0.99
THDi at full load <3% linear load, <5% nonlinear load
Battery
Battery (Vdc) ±192 (±180 ~ ±276 settable)
Charging Current (A) N × 10 Maximum (N = the number of power module)
Output
Power Module (kVA) 30
Power Module Number 2 3 4
System Capacity (kVA) 60 90 120
Power Factor 1
Voltage (Vac) 3Φ4W+PE, L-L:380,400,415 ±1%
Frequency (Hz) 50/60± 0.2% (battery mode)
Three Phase Difference True sine wave, ≤1 degrees
THDv ≤1% (linear load, full load); ≤4% (nonlinear load, full load)
Static Bypass Transfer Time 0
System Efficiency (MAX) 96%
Overload Capacity 101-105% continuous, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
Others
Display 7-inch Touch screen+ LED+ Physical buttons
Operating Temperature (ºC) 0~40
Storage Temperature (ºC) -40~70
Relative Humidity 0~95%, no condensation
Communication Function RS232, RS485, Dry contact, MODBUS, SNMP (optional)
Noise (dB) 70
Altitude(m) 0~2000, no derate
Cabling Bottom
Color Jet black RAL 9005
Power Module Dimension (W×D×H) (mm) 500×700×130
Cabinet Dimension (W×D×H) (mm)
Weight (kg) Cabinet 182
Power Module 24 kg per module
MODEL X-PND 100 X-PND 150 X-PND 200 X-PND 250 X-PND 300
Power module Model X-PND 100
Input
Voltage Range (Vac) 3Φ4W+PE, 380/400/415, L-L: 138~485
Input Wiring 3Ph+N+PE
Input Frequency (Hz) 40-70
Bypass Voltage Range (Vac) -15% (-20%/-30% optional) ~+15%(+10% /+20% optional)
Power Factor ≥0.99
THDi at full load <3% linear load, <5% nonlinear load
Battery
Battery (Vdc) ±192 (±180 ~ ±276 settable)
Charging Current (A) N × 10 Maximum (N = the number of power module)
Output
Power Module (kVA) 60
Power Module Number 2 3 4 5 6
System Capacity (kVA) 100 150 200 250 300
Power Factor 1
Voltage (Vac) 3Φ4W+PE, L-L:380,400,415 ±1%
Frequency (Hz) 50/60± 0.2% (battery mode)
Three Phase Difference True sine wave, ≤1 degrees
THDv ≤1% (linear load, full load); ≤4% (nonlinear load, full load)
Static Bypass Transfer Time 0
System Efficiency (MAX) 96%
Overload Capacity 101-105% continuous, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
Others
Display 7-inch Touch screen+ LED+ Physical buttons
Operating Temperature (ºC) 0~40
Storage Temperature (ºC) -40~70
Relative Humidity 0~95%, no condensation
Communication Function RS232, RS485, Dry contact, MODBUS, SNMP (optional)
Noise (dB) <70
Altitude(m) 0~2000, no derate
Cabling Bottom
Color Light grey RAL 7035
Power Module Dimension (W×D×H) (mm) 500×700×130
Cabinet Dimension (W×D×H) (mm) 600×860×2000
Weight (kg) Cabinet 182 218 247 257 263
Power Module 33 kg per module
MODEL X-PND 400 X-PND 500 X-PND 600 X-PND 800 X-PND 1000 X-PND 1200
Power module Model XPD-100
Input
Voltage Range (Vac) 3Φ4W+PE, 380/400/415, L-L: 138~485
Input Wiring 3Ph+N+PE
Input Frequency (Hz) 40-70
Bypass Voltage Range (Vac) -20% (10/15/30/40/50/60%) ~ +15% (10/20/25%)
Power Factor ≥0.99
THDi at full load <3% linear load
Battery
Battery Voltage (Vdc)* ±240 (±180~±300 settable)
Charging Current (A) N×30 Maximum (N = the number of power module)
Output
Power Module (kVA) 100
Power Module Number 4 5 6 8 10 12
System Capacity (kVA) 400 500 600 800 1000 1200
Power Factor 1
Voltage (Vac) 3Φ4W+PE, L-L:380,400,415 ±1%
Frequency (Hz) 50/60± 0.2% (battery mode)
Three Phase Difference True sine wave, ≤2 degrees
THDv ≤1% (linear load, full load); ≤4% (nonlinear load, full load)
Static Bypass Transfer Time 0
System Efficiency (MAX) 97%
Overload Capacity 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
Others
Display 7-inch Touch screen+ LED+ Physical buttons
Operating Temperature (ºC) 0~40
Storage Temperature (ºC) -40~70
Relative Humidity 0~95%, no condensation
Communication Function RS232, RS485, Dry contact, MODBUS, SNMP (optional)
Noise (dB) 70
Altitude(m) 0~2000, no derate
Cabling Bottom/Top Top
Color Light grey RAL 7035
Power Module Dimension (W×D×H) (mm) 500×750×130(3U)
Cabinet Dimension(W×D×H) (mm) 1200×1000×2000 1400x1000×2000 1800x1000×2000
Weight (kg) Cabinet 400 506 580 650 740
Power Module 55 kg per module