The TECNED OM(D) inverter series is available with input voltages from 24Vdc to 220Vdc nominal and single phase output. The OM(D) inverters are available in capacities from 5 kVA up to 100 kVA depending on DC voltage levels.

OM (D) inverter can be supplied as standard or fault tolerant systems within a single enclosure to meet customer requirements for safety and reliability.

The OM-D model includes an additional digital controller with LCD display that shows the systems current state of operation and system values, allows setting of system parameters and includes event and alarm logs.

Option list (OM-D)

  • Extend to 12x PFC (NO/NC) with LED
  • Fan failure alarm
  • Individual fuse failure indicator
  • DC ground fault
  • Over temperature
  • Up to 6 (DIN 96) meters / cabinet
  • RS485 / Modbus communication (OM-D only)
Input Nominal voltage 24 / 48 / 110 (125) / 220 Vdc
Voltage range -15% / +45%
Output Voltage 220 / 230 / 240 Vac / 1Ph + N
Static stability +/- 1%
Dynamic stability +/- 3% (0-100-0% load step)
Recovery time < 10 msec
Voltage THD Max 1.5% for 100% linear load
Frequency 50Hz / 60Hz (selectable)
Frequency stability +/- 0.1% (free running)
Power factor 0.9 PF Lag
General Ambient temperature -20 to +70 °C storage / -10 to +40 °C operation
Altitude above sea level 1000 m
Enclosure Aluzinc frame / powder coat RAL 7035
Standards Safety IEC/EN 62040-1 / EMC 55011
Conformity IEC 60146 / CE-Label